Loading...

Results based on a typical use case
| Appliance | Power | Usage/day | Wh/day |
|---|---|---|---|
| Compression fridge | 45W | 24h | 1080 |
| LED lighting | 20W | 4h | 80 |
| Water pump | 30W | 0.5h | 15 |
| Phone charging | 15W | 2h | 30 |
| Daily consumption | 1205 Wh | ||
Adjust these values with the calculator below
YOUR ENERGY PROFILE.
This document contains the sizing of your future electrical installation, calculated based on your appliances.
Inventory:
To guarantee 0WH without damaging your bank (80% max discharge):
Minimum power required to recharge your consumption:
Maximum power (with 25% safety margin).
Use this professional reference table to select the correct gauge (mm²) for your cables. For 12V in a van, the maximum tolerated voltage drop is 3%. Always use multi-stranded flexible automotive wire.
| Current (A) | Round trip < 2m | Round trip 4m | Round trip 6m |
|---|---|---|---|
| 5A (LEDs, USB) | 1.5 mm² | 2.5 mm² | 4 mm² |
| 10A (Fridge, Pump) | 2.5 mm² | 4 mm² | 6 mm² |
| 20A (Heater) | 4 mm² | 10 mm² | 10 mm² |
| 50A (DC/DC Booster) | 10 mm² | 16 mm² | 25 mm² |
| 100A (Inverter) | 25 mm² | 35 mm² | 50 mm² |
The fuse protects the wire, not the appliance. Always place it as close to the power source as possible (battery or busbar).
0W
0 Ah
Lithium LiFePO4
Pompe, Leds, Frigo...
NON REQUI
SHOPPING LIST
Where to find this equipment? Here is the community-approved selection.
12V 6-way Fuse Box
Mandatory protection
Digital Multimeter
Test your connections
Heavy Duty Crimping Tool
For perfect lugs
Heat Shrink Tubing
Insulation and safety
Let's break this checklist down component by component. First, batteries: if you're building a 48V bank from individual cells, you need a BMS that supports 16S configuration (16 cells x 3.2V nominal = 51.2V). The BMS charge cutoff should be 58.4V (3.65V per cell) and discharge cutoff around 44.8V (2.8V per cell). I run my LiFePO4 bank to about 85% DoD — that's the sweet spot between capacity and cycle life, giving me 2000-3000+ cycles easily.
Second, grounding. At 48V, you're above the 50V DC threshold that some codes consider hazardous. Your negative bus should connect to chassis ground at one single point. Run a proper ground fault protection setup. If your BMS has a ground fault detection feature, enable it.
Third, shore power integration. Your converter/charger needs 48V output capability. The Victron Skylla-IP65 48/25 or similar units handle this. If you're also doing alternator charging, you need a 48V DC-DC charger — the Victron Orion XS 48/48 or a dedicated alternator-to-48V unit. Not many B2B chargers support 48V natively, so plan this early.
Fourth, wire sizing. Even though currents are lower at 48V, don't cheap out. For a 3000W inverter pulling 62.5A, I'd run 16mm² (6 AWG) minimum for runs under 1.5m, 25mm² (4 AWG) for longer runs. Calculate your voltage drop — keep it under 3% on the main battery-to-inverter run.
Fifth, BMS communication. If you're using a Victron setup, check that your BMS can communicate via CAN bus or VE.Can with the Cerbo GX. Popular BMS options like the JK BMS or Daly BMS have varying levels of integration. The Victron-compatible ones (like REC BMS) cost more but save headaches. Without proper communication, your inverter won't know when the BMS triggers a cutoff, which can cause hard shutdowns and potential damage.
Finally, solar array configuration. With 48V batteries, you need higher panel voltage to give the MPPT controller enough headroom. Two 400W panels in series give you around 80-84V Voc — plenty of room for a 48V charge. Three in series pushes you to 120-126V Voc, which still fits under most 150V-rated controllers but check your cold-weather Voc carefully.