Loading...

Results based on a typical use case
| Appliance | Power | Usage/day | Wh/day |
|---|---|---|---|
| Compression fridge | 45W | 24h | 1080 |
| LED lighting | 20W | 4h | 80 |
| Water pump | 30W | 0.5h | 15 |
| Phone charging | 15W | 2h | 30 |
| Daily consumption | 1205 Wh | ||
Adjust these values with the calculator below
YOUR ENERGY PROFILE.
This document contains the sizing of your future electrical installation, calculated based on your appliances.
Inventory:
To guarantee 0WH without damaging your bank (80% max discharge):
Minimum power required to recharge your consumption:
Maximum power (with 25% safety margin).
Use this professional reference table to select the correct gauge (mm²) for your cables. For 12V in a van, the maximum tolerated voltage drop is 3%. Always use multi-stranded flexible automotive wire.
| Current (A) | Round trip < 2m | Round trip 4m | Round trip 6m |
|---|---|---|---|
| 5A (LEDs, USB) | 1.5 mm² | 2.5 mm² | 4 mm² |
| 10A (Fridge, Pump) | 2.5 mm² | 4 mm² | 6 mm² |
| 20A (Heater) | 4 mm² | 10 mm² | 10 mm² |
| 50A (DC/DC Booster) | 10 mm² | 16 mm² | 25 mm² |
| 100A (Inverter) | 25 mm² | 35 mm² | 50 mm² |
The fuse protects the wire, not the appliance. Always place it as close to the power source as possible (battery or busbar).
0W
0 Ah
Lithium LiFePO4
Pompe, Leds, Frigo...
NON REQUI
SHOPPING LIST
Where to find this equipment? Here is the community-approved selection.
12V 6-way Fuse Box
Mandatory protection
Digital Multimeter
Test your connections
Heavy Duty Crimping Tool
For perfect lugs
Heat Shrink Tubing
Insulation and safety
That table assumes short cable runs. If your inverter is more than 1.5m from the battery, go one gauge thicker. Voltage drop at 185A over 2 meters of 50mm² cable is about 0.3V — that's 55W of heat being generated in the cable continuously. Over 3 meters, double that. At these currents, the cable is basically a resistive heater. The fuse must be an ANL or MEGA type — standard blade fuses max out at 40A. Mount the fuse holder within 30cm of the battery positive terminal. This protects the entire cable run, not just the inverter. If the cable shorts against the chassis anywhere along its length, the fuse blows before the cable melts. One detail people miss: the negative cable must be the same gauge as the positive. Current flows in a loop — the return path carries the same amps. I've seen builds with 50mm² positive and 16mm² negative. That 16mm² cable was warm to the touch under load.